KRS-G75,
Screw Water Chilling Unit Capacity Rating
|
3470RPM R22
|
|
Cond.Temp.& Gauge Pressure
|
Ice Water Outlet
|
Ice Water Outlet/ InletTemp.Differential Deg.
|
Cooling Capacity Kcal/Hr.
|
RT
|
Input
KW
|
Chiller Ice water quantity
|
30
11.2
(160 PSI)
|
12.5
|
5.84
|
288,510
|
95.4
|
58.4
|
(1)
Design Ref.Value. (about)
53.2M/HR
Water Pressure
(2)
This ice water of the Outlet/ Inlet differential temperature
can be calculated, according to the design ref. value of the
cooling capacity of this data
|
10.0
|
5.30
|
265,000
|
87.6
|
57.5
|
7.5
|
4.72
|
241,890
|
80.0
|
56.6
|
5.0
|
4.28
|
218,760
|
72.3
|
56.4
|
35
12.9
(184 PSI)
|
12.5
|
5.46
|
271,830
|
89.9
|
66.5
|
10.0
|
5.00
|
249,090
|
82.4
|
65.4
|
7.5
|
4.56
|
226,330
|
74.8
|
64.5
|
5.0
|
4.12
|
204,730
|
67.7
|
64.2
|
40
14.7
(210 PSI)
|
12.5
|
5.20
|
258,570
|
85.5
|
71.4
|
10.0
|
4.73
|
236,950
|
78.4
|
70.7
|
7.5
|
4.28
|
216,100
|
71.5
|
69.9
|
5.0
|
3.87
|
196,000
|
64.8
|
69.8
|
45
16.7
(239 PSI)
|
12.5
|
4.94
|
239,980
|
79.4
|
79.4
|
10.0
|
4.48
|
219,130
|
72.5
|
78.3
|
7.5
|
4.05
|
198,660
|
65.7
|
77.4
|
5.0
|
3.66
|
179,700
|
59.4
|
77.1
|
The design ref. value of the cooling water
quantity for the condenser.
|
Cooling water inlet
|
22
|
27
|
32
|
37
|
The cooling water quantity (about)
|
63.8M /HR
|
Cooling water outlet
|
27
|
32
|
37
|
42
|
Water pressure
|
Max.4
|
Cond. temp.
|
30
|
35
|
40
|
45
|
Note 1: This Information Shows the Refrigerating Performance and Testing
Data of This Company.
Note 2:Permissible Inspection Value
|