KRS-G75, Screw Water Chilling Unit Capacity Rating
3470RPM R22
Cond.Temp.& Gauge Pressure
Ice Water Outlet
Ice Water Outlet/ InletTemp.Differential Deg.
Cooling Capacity Kcal/Hr.
RT
Input
KW
Chiller Ice water quantity
30
11.2
(160 PSI)
12.5
5.84
288,510
95.4
58.4


(1)
Design Ref.Value. (about)
53.2M/HR

Water Pressure

(2)
This ice water of the Outlet/ Inlet differential temperature can be calculated, according to the design ref. value of the cooling capacity of this data

10.0
5.30
265,000
87.6
57.5
7.5
4.72
241,890
80.0
56.6
5.0
4.28
218,760
72.3
56.4
35
12.9
(184 PSI)
12.5
5.46
271,830
89.9
66.5
10.0
5.00
249,090
82.4
65.4
7.5
4.56
226,330
74.8
64.5
5.0
4.12
204,730
67.7
64.2
40
14.7
(210 PSI)
12.5
5.20
258,570
85.5
71.4
10.0
4.73
236,950
78.4
70.7
7.5
4.28
216,100
71.5
69.9
5.0
3.87
196,000
64.8
69.8
45
16.7
(239 PSI)
12.5
4.94
239,980
79.4
79.4
10.0
4.48
219,130
72.5
78.3
7.5
4.05
198,660
65.7
77.4
5.0
3.66
179,700
59.4
77.1

The design ref. value of the cooling water quantity for the condenser.
Cooling water inlet
22
27
32
37
The cooling water quantity (about)
63.8M/HR
Cooling water outlet
27
32
37
42
Water pressure
Max.4
Cond. temp.
30
35
40
45

Note 1: This Information Shows the Refrigerating Performance and Testing Data of This Company.
Note 2:Permissible Inspection Value