2KRS-G120, Screw Water Chilling Unit Capacity Rating
3470RPM R22
Cond.Temp.& Gauge Pressure
Ice Water Outlet
Ice Water Outlet/ InletTemp.Differential Deg.
Cooling Capacity Kcal/Hr.
RT
Input
KW
Chiller Ice water quantity
30
11.2
(160 PSI)
12.5
5.84
460,250
152.2
93.0


(1)
Design Ref.Value. (about)
79.8M/HR

Water Pressure

(2)
This ice water of the Outlet/ Inlet differential temperature can be calculated, according to the design
ref. value of the cooling capacity of this data

 

10.0
5.30
422,760
139.8
91.6
7.5
4.72
385,860
127.6
90.2
5.0
4.28
348,970
115.4
90.0
35
12.9
(184 PSI)
12.5
5.46
433,640
143.4
106.0
10.0
5.00
397,350
131.4
104.4
7.5
4.56
361,070
119.4
102.8
5.0
4.12
326,590
108.0
102.4
40
14.7
(210 PSI)
12.5
5.20
412,470
136.4
113.8
10.0
4.73
378,000
125.0
112.6
7.5
4.28
344,740
114.0
111.4
5.0
3.87
312,680
103.4
111.2
45
16.7
(239 PSI)
12.5
4.94
382,840
126.6
126.6
10.0
4.48
349,570
115.6
125.0
7.5
4.05
316,920
104.8
123.4
5.0
3.66
286,680
94.8
123.0

The design ref. value of the cooling water quantity for the condenser.
Cooling water inlet
22
27
32
37
The cooling water quantity (about)
95.6M/HR
Cooling water outlet
27
32
37
42
Water pressure
Max.4
Cond. temp.
30
35
40
45
Note 1: This Information Shows the Refrigerating Performance and Testing Data of This Company.
Note 2:Permissible Inspection Value