2KRS-G120,
Screw Water Chilling Unit Capacity Rating |
3470RPM R22
|
|
Cond.Temp.& Gauge Pressure
|
Ice Water Outlet
|
Ice Water Outlet/ InletTemp.Differential Deg.
|
Cooling Capacity Kcal/Hr.
|
RT
|
Input
KW
|
Chiller Ice water quantity
|
30
11.2
(160 PSI)
|
12.5
|
5.84
|
460,250
|
152.2
|
93.0
|
(1)
Design Ref.Value. (about)
79.8M/HR
Water Pressure
(2)
This ice water of the Outlet/ Inlet differential temperature
can be calculated, according to the design
ref. value of the cooling capacity of this data
|
10.0
|
5.30
|
422,760
|
139.8
|
91.6
|
7.5
|
4.72
|
385,860
|
127.6
|
90.2
|
5.0
|
4.28
|
348,970
|
115.4
|
90.0
|
35
12.9
(184 PSI)
|
12.5
|
5.46
|
433,640
|
143.4
|
106.0
|
10.0
|
5.00
|
397,350
|
131.4
|
104.4
|
7.5
|
4.56
|
361,070
|
119.4
|
102.8
|
5.0
|
4.12
|
326,590
|
108.0
|
102.4
|
40
14.7
(210 PSI)
|
12.5
|
5.20
|
412,470
|
136.4
|
113.8
|
10.0
|
4.73
|
378,000
|
125.0
|
112.6
|
7.5
|
4.28
|
344,740
|
114.0
|
111.4
|
5.0
|
3.87
|
312,680
|
103.4
|
111.2
|
45
16.7
(239 PSI)
|
12.5
|
4.94
|
382,840
|
126.6
|
126.6
|
10.0
|
4.48
|
349,570
|
115.6
|
125.0
|
7.5
|
4.05
|
316,920
|
104.8
|
123.4
|
5.0
|
3.66
|
286,680
|
94.8
|
123.0
|
The design ref. value of the cooling water
quantity for the condenser.
|
Cooling water inlet
|
22
|
27
|
32
|
37
|
The cooling water quantity (about)
|
95.6M /HR
|
Cooling water outlet
|
27
|
32
|
37
|
42
|
Water pressure
|
Max.4
|
Cond. temp.
|
30
|
35
|
40
|
45
|
Note 1: This Information Shows
the Refrigerating Performance and Testing Data of This Company.
Note 2:Permissible Inspection Value
|