KRS-G50,
Screw Water Chilling Unit Capacity Rating |
3470RPM R22
|
|
Cond.Temp.& Gauge Pressure
|
Ice Water Outlet
|
Ice Water Outlet/InletTemp.Differential Deg.
|
Cooling Capacity Kcal/Hr.
|
RT
|
Input KW
|
Chiller Ice water quantity
|
30
11.
(160 PSI)
|
12.5
|
5.84
|
192,340
|
63.6
|
38.9
|
(1)
Design Ref.Value. (about)
33.3M/HR
Water Pressure
(2)
This ice water of the Outlet/ Inlet differential temperature
can be calculated, according to the design ref value of the
cooling capacity of this data
|
10.0
|
5.30
|
176,670
|
58.4
|
38.3
|
7.5
|
4.72
|
161,260
|
53.3
|
37.7
|
5.0
|
4.28
|
145,840
|
48.2
|
37.6
|
35
12.9
(184 PSI)
|
12.5
|
5.46
|
181,220
|
59.9
|
44.3
|
10.0
|
5.00
|
166,060
|
54.9
|
43.6
|
7.5
|
4.56
|
150,890
|
49.9
|
43.0
|
5.0
|
4.12
|
136,490
|
45.1
|
42.8
|
40
14.7
(210 PSI)
|
12.5
|
5.20
|
172,380
|
57.0
|
47.6
|
10.0
|
4.73
|
157,970
|
52.2
|
47.1
|
7.5
|
4.28
|
144,070
|
47.6
|
46.6
|
5.0
|
3.87
|
130,670
|
43.2
|
46.5
|
45
16.7
(239 PSI)
|
12.5
|
4.94
|
159,990
|
52.9
|
52.9
|
10.0
|
4.48
|
146,090
|
48.3
|
52.2
|
7.5
|
4.05
|
132,440
|
43.8
|
51.6
|
5.0
|
3.66
|
119,800
|
39.6
|
51.4
|
The design ref. value of the cooling water
quantity for the condenser.
|
Cooling water inlet
|
22
|
27
|
32
|
37
|
The cooling water quantity (about)
|
39.9M /HR
|
Cooling water outlet
|
27
|
32
|
37
|
42
|
Water pressure
|
Max.4
|
Cond. temp.
|
30
|
35
|
40
|
45
|
Note
1: This Information Shows the Refrigerating Performance and Testing
Data of This Company.
Note 2:Permissible Inspection Value
|