2KRS-G100, Screw Water Chilling Unit Capacity Rating
3470RPM R22
Cond.Temp.& Gauge Pressure
Ice Water OIutlet
Ice Water Outlet/ InletTemp.Differential Deg.
Cooling Capacity Kcal/Hr.
RT
Input
KW
Chiller Ice water quantity
30
11.2
(160 PSI)
12.5
5.84
384,690
127.2
77.7


(1)
Design Ref.Value. (about)
66.6M/HR

Water Pressure

(2)
This ice water of the Outlet/ Inlet differential temperature can be calculated, according to the design ref. value of the cooling capacity of this data

10.0
5.30
353,350
116.8
76.6
7.5
4.72
322,510
106.7
75.4
5.0
4.28
291,680
96.5
75.2
35
12.9
(184 PSI)
12.5
5.46
362,450
119.9
88.6
10.0
5.00
332,120
109.8
87.3
7.5
4.56
301,790
99.8
85.9
5.0
4.12
272,970
90.3
85.6
40
14.7
(210 PSI)
12.5
5.20
344,750
114.0
95.1
10.0
4.73
315,940
104.5
94.1
7.5
4.28
288,140
95.3
93.1
5.0
3.87
261,350
86.4
92.9
45
16.7
(239 PSI)
12.5
4.94
319,980
105.8
105.8
10.0
4.48
292,180
96.6
104.5
7.5
4.05
264,880
87.6
103.1
5.0
3.66
239,610
79.2
102.8

The desgn ref. value of the cooling water quantity for the condenser.
Cooling water inlet
22
27
32
37
The cooling water quantity (about)
79.8M/HR
Cooling water outlet
27
32
37
42
Water pressure
Max.4
Cond. temp.
30
35
40
45
Note 1: This Information Shows the Refrigerating Performance and Testing Data of This Company.
Note 2:Permissible Inspection Value