2KRS-G100,
Screw Water Chilling Unit Capacity Rating
|
3470RPM R22
|
|
Cond.Temp.& Gauge Pressure
|
Ice Water OIutlet
|
Ice Water Outlet/ InletTemp.Differential Deg.
|
Cooling Capacity Kcal/Hr.
|
RT
|
Input
KW
|
Chiller Ice water quantity
|
30
11.2
(160 PSI)
|
12.5
|
5.84
|
384,690
|
127.2
|
77.7
|
(1)
Design Ref.Value. (about)
66.6M/HR
Water Pressure
(2)
This ice water of the Outlet/ Inlet differential temperature
can be calculated, according to the design ref. value of the
cooling capacity of this data
|
10.0
|
5.30
|
353,350
|
116.8
|
76.6
|
7.5
|
4.72
|
322,510
|
106.7
|
75.4
|
5.0
|
4.28
|
291,680
|
96.5
|
75.2
|
35
12.9
(184 PSI)
|
12.5
|
5.46
|
362,450
|
119.9
|
88.6
|
10.0
|
5.00
|
332,120
|
109.8
|
87.3
|
7.5
|
4.56
|
301,790
|
99.8
|
85.9
|
5.0
|
4.12
|
272,970
|
90.3
|
85.6
|
40
14.7
(210 PSI)
|
12.5
|
5.20
|
344,750
|
114.0
|
95.1
|
10.0
|
4.73
|
315,940
|
104.5
|
94.1
|
7.5
|
4.28
|
288,140
|
95.3
|
93.1
|
5.0
|
3.87
|
261,350
|
86.4
|
92.9
|
45
16.7
(239 PSI)
|
12.5
|
4.94
|
319,980
|
105.8
|
105.8
|
10.0
|
4.48
|
292,180
|
96.6
|
104.5
|
7.5
|
4.05
|
264,880
|
87.6
|
103.1
|
5.0
|
3.66
|
239,610
|
79.2
|
102.8
|
The desgn ref. value of the cooling water
quantity for the condenser.
|
Cooling water inlet
|
22
|
27
|
32
|
37
|
The cooling water quantity (about)
|
79.8M /HR
|
Cooling water outlet
|
27
|
32
|
37
|
42
|
Water pressure
|
Max.4
|
Cond. temp.
|
30
|
35
|
40
|
45
|
Note 1: This Information Shows
the Refrigerating Performance and Testing Data of This Company.
Note 2:Permissible Inspection Value
|