KRS-G40,
Screw Water Chilling Unit Capacity Rating
|
3470RPM R22
|
|
Cond.Temp.& Gauge
Pressure
|
Ice Water Outlet
|
Ice Water Outlet/
InletTemp.Differential Deg.
|
Cooling Capacity
Kcal/Hr.
|
RT
|
Input
KW
|
Chiller Ice water quantity
|
30
11.2
(160 PSI)
|
12.5
|
5.84
|
154,560
|
51.1
|
31.2
|
(1)
Design Ref.Value.
(about)
26.6M/HR
Water Pressure
(2)
This ice water of the Outlet/
Inlet differential temperature can be calculated, according
to the design ref. value of the cooling capacity of this data
|
10.0
|
5.30
|
141,970
|
46.9
|
30.8
|
7.5
|
4.72
|
129,580
|
42.9
|
30.3
|
5.0
|
4.28
|
117,190
|
38.8
|
30.2
|
35
12.9
(184 PSI)
|
12.5
|
5.46
|
145,630
|
48.2
|
35.6
|
10.0
|
5.00
|
133,440
|
44.1
|
35.1
|
7.5
|
4.56
|
121,250
|
40.1
|
34.5
|
5.0
|
4.12
|
109,680
|
36.3
|
34.4
|
40
14.7
(210 PSI)
|
12.5
|
5.20
|
138,520
|
45.8
|
38.2
|
10.0
|
4.73
|
126,940
|
42.0
|
37.8
|
7.5
|
4.28
|
115,770
|
38.3
|
37.4
|
5.0
|
3.87
|
105,010
|
34.7
|
37.3
|
45
16.7
(239 PSI)
|
12.5
|
4.94
|
128,570
|
42.5
|
42.5
|
10.0
|
4.48
|
117,390
|
38.8
|
42.0
|
7.5
|
4.05
|
106,430
|
35.2
|
41.4
|
5.0
|
3.66
|
96,270
|
31.8
|
41.3
|
The design ref. value
of the cooling water quantity for the condenser.
|
Cooling water inlet
|
22
|
27
|
32
|
37
|
The cooling water
quantity
(about)
|
31.9M /HR
|
Cooling water outlet
|
27
|
32
|
37
|
42
|
Water pressure
|
Max.4
|
Cond. temp.
|
30
|
35
|
40
|
45
|
Note
1: This Information Shows the Refrigerating Performance and Testing
Data of This Company.
Note 2:Permissible Inspection Value
|