2KRS-G150,
Screw Water Chilling Unit Capacity Rating |
3470RPM R22
|
|
Cond.Temp.& Gauge Pressure
|
Ice Water Outlet
|
Ice Water Outlet/InletTemp. Differential Deg.
|
Cooling Capacity Kcal/Hr.
|
RT
|
Input
KW
|
Chiller Ice water quantity
|
30
11.2
(160 PSI)
|
12.5
|
5.84
|
577,020
|
190.8
|
116.7
|
(1)
Design Ref.Value. (about)
106.4M/HR
Water Pressure
(2)
This ice water of the Outlet/ Inlet differential temperature
can be calculated, according to the design ref. value of the
cooling capacity of this data
|
10.0
|
5.30
|
530,000
|
175.3
|
114.9
|
7.5
|
4.72
|
483,780
|
160.0
|
113.1
|
5.0
|
4.28
|
437,520
|
144.7
|
112.8
|
35
12.9
(184 PSI)
|
12.5
|
5.46
|
543,660
|
179.8
|
132.9
|
10.0
|
5.00
|
488,180
|
164.7
|
130.8
|
7.5
|
4.56
|
452,660
|
149.7
|
129.0
|
5.0
|
4.12
|
409,460
|
135.4
|
128.4
|
40
14.7
(210 PSI)
|
12.5
|
5.20
|
517,140
|
171.0
|
142.8
|
10.0
|
4.73
|
473,900
|
156.7
|
141.3
|
7.5
|
4.28
|
432,200
|
142.9
|
139.8
|
5.0
|
3.87
|
392,000
|
129.6
|
139.5
|
45
16.7
(239 PSI)
|
12.5
|
4.94
|
479,960
|
158.7
|
158.7
|
10.0
|
4.48
|
438,260
|
144.9
|
156.6
|
7.5
|
4.05
|
397,320
|
131.4
|
154.8
|
5.0
|
3.66
|
359,400
|
118.8
|
154.2
|
The design ref. value of the cooling water
quantity for the condenser.
|
Cooling water inlet
|
22
|
27
|
32
|
37
|
The cooling water quantity (about)
|
127.6M /HR
|
Cooling water outlet
|
27
|
32
|
37
|
42
|
Water pressure
|
Max.4
|
Cond. temp.
|
30
|
35
|
40
|
45
|
Note 1: This Information Shows
the Refrigerating Performance and Testing Data of This Company.
Note 2:Permissible Inspection Value
|