2KRS-G80, Screw Water Chilling Unit Capacity Rating
3470RPM R22
Cond.Temp.& Gauge Pressure
Ice Water Outlet
Ice Water Outlet/ InletTemp.Differential Deg.
Cooling Capacity Kcal/Hr.
RT
Input
KW
Chiller Ice water quantity
30
11.2
(160 PSI)
12.5
5.84
309,130
102.2
62.5

(1)
Design Ref.Value. (about)
53.2M/HR

Water Pressure

(2)
This ice water of the Outlet/ Inlet differential temperature can be calculated, according to the design ref. value of the cooling capacity of this data

10.0
5.30
283,940
93.9
61.5
7.5
4.72
259,160
85.7
60.6
5.0
4.28
234,380
77.5
60.4
35
12.9
(184 PSI)
12.5
5.46
291,250
96.3
71.2
10.0
5.00
266,880
88.3
70.1
7.5
4.56
242,510
80.2
69.0
5.0
4.12
219,350
72.5
68.8
40
14.7
(210 PSI)
12.5
5.20
277,030
91.6
76.4
10.0
4.73
253,880
84.0
75.6
7.5
4.28
231,540
76.6
74.8
5.0
3.87
210,010
69.4
74.7
45
16.7
(239 PSI)
12.5
4.94
257,130
85.0
85.0
10.0
4.48
234,790
77.6
84.0
7.5
4.05
212,850
70.4
82.9
5.0
3.66
192,540
63.7
82.6

The design ref. value of the cooling water quantity for the condenser.
Cooling water inlet
22
27
32
37
The cooling water quantity (about)
63.8M/HR
Cooling water outlet
27
32
37
42
Water pressure
Max.4
Cond. temp.
30
35
40
45
Note 1: This Information Shows the Refrigerating Performance and Testing Data of This Company.
Note 2:Permissible Inspection Value