The
ref. design value of the chilling water quantity, the cooing
water quantity and suggest installation cooling tower
|
Model
|
Chilling water pump
|
Cooling water pump
|
Suggestion cooling tower
RT
|
Water quantity
(Ref. design value)
|
Water quantity
(Ref. design value)
|
TPH
|
LPM
|
GPM
|
Ref. design value.
(about)
|
TPH
|
LPM
|
GPM
|
Ref. design value.
(about)
|
KRS-G40
|
26.6
|
443
|
118
|
(1)
Ice water
Outlet/Inlet
Temp.
differential
degree
(2)
Pressure drop.
|
31.9
|
531
|
141
|
(1)
Ice water
Outlet/Inlet
Temp.
differential
degree
(2)
Pressure drop.
|
60
|
KRS-G50
|
33.3
|
556
|
146
|
39.9
|
666
|
176
|
80
|
KRS-G60
|
39.9
|
666
|
176
|
47.8
|
798
|
211
|
100
|
KRS-G75
|
53.2
|
886
|
236
|
63.8
|
1062
|
282
|
125
|
2KRS-G80
|
53.2
|
886
|
236
|
63.8
|
1062
|
282
|
125
|
2KRS-G100
|
66.6
|
1112
|
292
|
79.8
|
1332
|
352
|
150
|
2KRS-G120
|
79.8
|
1332
|
352
|
95.6
|
1596
|
422
|
175
|
2KRS-G150
|
106.4
|
1772
|
472
|
127.6
|
2126
|
562
|
225
|