| 半密閉螺旋式 | |||||||
| Semihermetic Screw | |||||||
| 2KRS-G200螺旋式冷媒壓縮機冷凍特性表 | R22 | ||||||
| Screw Freon Compressor Capacity Rating | 3470RPM | ||||||
| 凝縮溫度 | 蒸發溫度 | 蒸發壓力 | 冷卻能力 | 冷凍噸 | 輸入電力 | ||
| 和表壓力 | Suction Pressure | ||||||
| Cond.Temp. & | Suction Temp. | (Gauge ) | Cooling Capacity | Input | |||
| Gauge Pressure | ℃ | lb/in2 | kg/cm2 | Kcal/Hr | RT | KW | |
| -40 | 0.6 | 0.04 | 117,940 | 39.0 | 129.2 | ||
| -35 | 4.6 | 0.32 | 155,430 | 51.4 | 130.2 | ||
| -30 | 9.2 | 0.65 | 191,720 | 63.4 | 131.4 | ||
| 30℃ | -25 | 14.5 | 1.02 | 236,480 | 78.2 | 132.4 | |
| 11.2kg/cm2 | -20 | 21.0 | 1.48 | 280,020 | 92.6 | 136.4 | |
| (160 PSI) | -15 | 28.4 | 2.00 | 349,570 | 115.6 | 139.6 | |
| -10 | 37.0 | 2.60 | 422,150 | 139.6 | 142.4 | ||
| -5 | 46.6 | 3.28 | 509,240 | 168.4 | 149.6 | ||
| 0 | 57.9 | 4.07 | 630,810 | 208.6 | 150.0 | ||
| -35 | 4.6 | 0.32 | 125,800 | 41.6 | 148.8 | ||
| -30 | 9.2 | 0.65 | 165,720 | 54.8 | 150.0 | ||
| 35℃ | -25 | 14.5 | 1.02 | 204,420 | 67.6 | 151.2 | |
| 12.9kg/cm2 | -20 | 21.0 | 1.48 | 252,200 | 83.4 | 152.4 | |
| (184 PSI) | -15 | 28.4 | 2.00 | 320,540 | 106.0 | 155.6 | |
| -10 | 37.0 | 2.60 | 395,540 | 130.8 | 160.4 | ||
| -5 | 46.6 | 3.28 | 477,790 | 158.0 | 161.6 | ||
| 0 | 57.9 | 4.07 | 589,680 | 195.0 | 170.8 | ||
| -35 | 4.6 | 0.32 | 119,750 | 39.6 | 166.4 | ||
| -30 | 9.2 | 0.65 | 157,250 | 52.0 | 167.6 | ||
| 40℃ | -25 | 14.5 | 1.02 | 194,750 | 64.4 | 169.0 | |
| 14.7kg/cm2 | -20 | 21.0 | 1.48 | 240,110 | 79.4 | 170.4 | |
| (210 PSI) | -15 | 28.4 | 2.00 | 303,000 | 100.2 | 174.2 | |
| -10 | 37.0 | 2.60 | 374,980 | 124.0 | 176.6 | ||
| -5 | 46.6 | 3.28 | 458,440 | 151.6 | 180.2 | ||
| 0 | 57.9 | 4.07 | 563,070 | 186.2 | 185.4 | ||
| 註:1.冷凍特性試驗係依據吸入冷媒蒸氣過熱10℃,冷媒液體超冷5℃. | |||||||
| ※正常運轉時請調整冷媒蒸氣過熱溫度約5℃比較適合. | |||||||
| 2.使用於蒸發溫度-15℃以下時,高壓部將產生超高溫會影響冷凍油使之稀薄,需要增加裝置油冷卻器. | |||||||
| (Economizer Cooler) | |||||||
| 3.可容許檢驗值±5%. | |||||||
| NOTE:1.The Refrigerating Performance Based on 10℃ Suction Superheat , 5℃ Liquid Subcooling. | |||||||
| 2.The Suction Temp. below - 15℃ is in need of oil cooler (Economizer cooler). | |||||||
| 3.Permissible Inspection Value±5%. | |||||||