半密閉螺旋式 |
|
|
|
|
|
|
Semihermetic Screw |
|
KRS-G125螺旋式冷媒壓縮機冷凍特性表 |
|
R22 |
|
Screw
Freon Compressor Capacity Rating |
|
|
3470RPM |
凝縮溫度 |
蒸發溫度 |
蒸發壓力 |
冷卻能力 |
冷凍噸 |
輸入電力 |
和表壓力 |
|
Suction
Pressure |
|
|
|
|
Cond.Temp.
& |
Suction Temp. |
(Gauge ) |
Cooling Capacity |
|
Input |
Gauge Pressure |
℃ |
lb/in2 |
kg/cm2 |
Kcal/Hr |
RT |
KW |
|
-40 |
0.6 |
0.04 |
73,790 |
|
24.4 |
80.8 |
|
-35 |
4.6 |
0.32 |
97,070 |
|
32.1 |
81.4 |
|
-30 |
9.2 |
0.65 |
119,750 |
|
39.6 |
82.1 |
30℃ |
-25 |
14.5 |
1.02 |
147,870 |
|
48.9 |
82.8 |
11.2kg/cm2 |
-20 |
21.0 |
1.48 |
175,090 |
|
57.9 |
85.3 |
(160 PSI) |
-15 |
28.4 |
2.00 |
218,640 |
|
72.3 |
87.3 |
|
-10 |
37.0 |
2.60 |
264,000 |
|
87.3 |
89.0 |
|
-5 |
46.6 |
3.28 |
318,430 |
|
105.3 |
93.5 |
|
0 |
57.9 |
4.07 |
394,330 |
|
130.4 |
93.8 |
|
-35 |
4.6 |
0.32 |
78,620 |
|
26.0 |
93.0 |
|
-30 |
9.2 |
0.65 |
103,720 |
|
34.3 |
93.8 |
35℃ |
-25 |
14.5 |
1.02 |
127,920 |
|
42.3 |
94.5 |
12.9kg/cm2 |
-20 |
21.0 |
1.48 |
157,550 |
|
52.1 |
95.3 |
(184 PSI) |
-15 |
28.4 |
2.00 |
200,490 |
|
66.3 |
97.3 |
|
-10 |
37.0 |
2.60 |
247,360 |
|
81.8 |
100.3 |
|
-5 |
46.6 |
3.28 |
298,770 |
|
98.8 |
101.0 |
|
0 |
57.9 |
4.07 |
368,630 |
|
121.9 |
106.8 |
|
-35 |
4.6 |
0.32 |
75,000 |
|
24.8 |
104.0 |
|
-30 |
9.2 |
0.65 |
98,280 |
|
32.5 |
104.8 |
40℃ |
-25 |
14.5 |
1.02 |
121,870 |
|
40.3 |
105.6 |
14.7kg/cm2 |
-20 |
21.0 |
1.48 |
149,990 |
|
49.6 |
106.5 |
(210 PSI) |
-15 |
28.4 |
2.00 |
189,300 |
|
62.6 |
108.9 |
|
-10 |
37.0 |
2.60 |
234,360 |
|
77.5 |
110.4 |
|
-5 |
46.6 |
3.28 |
286,680 |
|
94.8 |
112.6 |
|
0 |
57.9 |
4.07 |
351,990 |
|
116.4 |
115.9 |
|
|
|
註:1.冷凍特性試驗係依據吸入冷媒蒸氣過熱10℃,冷媒液體超冷5℃. |
|
|
※正常運轉時請調整冷媒蒸氣過熱溫度約5℃比較適合. |
|
|
2.使用於蒸發溫度-15℃以下時,高壓部將產生超高溫會影響冷凍油使之稀薄,需要增加裝置油冷卻器. |
(Economizer Cooler) |
|
|
|
|
3.可容許檢驗值±5%. |
|
|
|
|
|
NOTE:1.The
Refrigerating Performance Based on 10℃ Suction Superheat , 5℃ Liquid Subcooling. |
|
2.The Suction Temp. below - 15℃ is in need of oil cooler (Economizer cooler). |
|
|
3.Permissible Inspection Value±5%. |
|
|
|
|
|
|
|
|
|
|
|
|
|