半密閉螺旋式
Semihermetic Screw
KRS-G30螺旋式冷媒壓縮機冷凍特性表       R22
  Screw Freon Compressor Capacity Rating      3470RPM
凝縮溫度 蒸發溫度 蒸發壓力 冷卻能力 冷凍噸 輸入電力
和表壓力   Suction Pressure      
Cond.Temp. &  Suction Temp. (Gauge ) Cooling Capacity   Input
Gauge Pressure lb/in2 kg/cm2 Kcal/Hr RT KW
  -40 0.6 0.04           17,840   5.9 19.4
  -35 4.6 0.32           23,280   7.7 19.5
  -30 9.2 0.65           28,730 9.5 19.7
30 -25 14.5 1.02           35,380   11.7 19.9
11.2kg/cm2 -20 21.0 1.48           42,030 13.9 20.5
(160 PSI) -15 28.4 2.00           52,320   17.3 20.9
  -10 37.0 2.60           63,200 20.9 21.4
  -5 46.6 3.28           76,510   25.3 22.4
  0 57.9 4.07           94,650   31.3 22.5
  -35 4.6 0.32           18,750   6.2 22.3
  -30 9.2 0.65           24,800 8.2 22.5
35 -25 14.5 1.02           30,540   10.1 22.7
12.9kg/cm2 -20 21.0 1.48           37,800 12.5 22.9
(184 PSI) -15 28.4 2.00           48,080   15.9 23.3
  -10 37.0 2.60           59,270 19.6 24.1
  -5 46.6 3.28           71,670   23.7 24.2
  0 57.9 4.07           88,600   29.3 25.6
  -35 4.6 0.32           17,840   5.9 25.0
  -30 9.2 0.65           23,590 7.8 25.1
40 -25 14.5 1.02           29,330   9.7 25.4
14.7kg/cm2 -20 21.0 1.48           35,990 11.9 25.6
(210 PSI) -15 28.4 2.00           45,360   15.0 26.1
  -10 37.0 2.60           56,250 18.6 26.5
  -5 46.6 3.28           68,640   22.7 27.0
  0 57.9 4.07           84,370   27.9 27.8
註:1.冷凍特性試驗係依據吸入冷媒蒸氣過熱10℃,冷媒液體超冷5℃.
             ※正常運轉時請調整冷媒蒸氣過熱溫度約5℃比較適合.
     2.使用於蒸發溫度-15℃以下時,高壓部將產生超高溫會影響冷凍油使之稀薄,需要增加裝置油冷卻器.
             (Economizer Cooler)
     .可容許檢驗值±5%.
NOTE:1.The Refrigerating Performance Based on 10 Suction Superheat , 5 Liquid Subcooling. 
           2.The Suction Temp. below - 15 is in need of oil cooler (Economizer cooler).
           3.Permissible Inspection Value±5%.