| 半密閉螺旋式 | |||||||
| Semihermetic Screw | |||||||
| RES-S93 螺旋式冷媒壓縮機冷凍特性表 | R134a | ||||||
| Screw Freon Compressor Capacity Rating | 3470RPM | ||||||
| 凝縮溫度 | 蒸發溫度 | 蒸發壓力 | 冷卻能力 | 冷凍噸 | 輸入電力 | ||
| 和表壓力 | Suction Pressure | ||||||
| Cond.Temp. & | Suction Temp. | (Gauge ) | Cooling Capacity | Input | |||
| Gauge Pressure | ℃ | lb/in2 | kg/cm2 | Kcal/Hr | RT | KW | |
| -25 | 1.4 | 0.1 | 69,550 | 23.0 | 44.6 | ||
| -20 | 4.3 | 0.3 | 89,210 | 29.5 | 47.6 | ||
| -15 | 9.9 | 0.7 | 120,360 | 39.8 | 50.5 | ||
| 30℃ | -10 | 14 | 1.0 | 155,740 | 51.5 | 53.4 | |
| 6.8 kg/cm2 | -5 | 21 | 1.5 | 198,370 | 65.6 | 57.9 | |
| (97 PSI) | 0 | 28 | 2.0 | 260,060 | 86.0 | 58.1 | |
| 5 | 35 | 2.5 | 316,310 | 104.6 | 59.9 | ||
| -20 | 4.3 | 0.3 | 80,440 | 26.6 | 53.3 | ||
| -15 | 9.9 | 0.7 | 110,380 | 36.5 | 56.4 | ||
| 35℃ | -10 | 14 | 1.0 | 147,870 | 48.9 | 60.4 | |
| 8.1 kg/cm2 | -5 | 21 | 1.5 | 186,280 | 61.6 | 62.6 | |
| (114 PSI) | 0 | 28 | 2.0 | 240,110 | 79.4 | 67.0 | |
| 5 | 35 | 2.5 | 297,560 | 98.4 | 69.1 | ||
| -20 | 4.3 | 0.3 | 76,510 | 25.3 | 59.6 | ||
| -15 | 9.9 | 0.7 | 104,330 | 34.5 | 64.1 | ||
| 40℃ | -10 | 14 | 1.0 | 138,800 | 45.9 | 67.9 | |
| 9.3 kg/cm2 | -5 | 21 | 1.5 | 179,320 | 59.3 | 70.9 | |
| (132 PSI) | 0 | 28 | 2.0 | 226,500 | 74.9 | 73.8 | |
| 5 | 35 | 2.5 | 281,530 | 93.1 | 75.9 | ||
| -15 | 9.9 | 0.7 | 97,980 | 32.4 | 71.9 | ||
| 45℃ | -10 | 14 | 1.0 | 128,820 | 42.6 | 75.8 | |
| 10.8 kg/cm2 | -5 | 21 | 1.5 | 161,780 | 53.5 | 79.1 | |
| (153 PSI) | 0 | 28 | 2.0 | 207,140 | 68.5 | 82.6 | |
| 5 | 35 | 2.5 | 257,950 | 85.3 | 84.6 | ||
| 註:1.冷凍特性試驗係依據吸入冷媒蒸氣過熱10℃,冷媒液體超冷5℃. | |||||||
| ※正常運轉時請調整冷媒蒸氣過熱溫度約5℃比較適合. | |||||||
| 2.使用於蒸發溫度-15℃以下時,高壓部將產生超高溫會影響冷凍油使之稀薄,需要增加裝置油冷卻器. | |||||||
| (Economizer Cooler) | |||||||
| 3.可容許檢驗值±5%. | |||||||
| NOTE:1.The Refrigerating Performance Based on 10℃ Suction Superheat , 5℃ Liquid Subcooling. | |||||||
| 2.The Suction Temp. below - 15℃ is in need of oil cooler (Economizer cooler). | |||||||
| 3.Permissible Inspection Value±5%. | |||||||