半密閉螺旋式
Semihermetic Screw
KRS-G300螺旋式冷媒壓縮機冷凍特性表       R22
  Screw Freon Compressor Capacity Rating      3470RPM
凝縮溫度 蒸發溫度 蒸發壓力 冷卻能力 冷凍噸 輸入電力
和表壓力   Suction Pressure      
Cond.Temp. &  Suction Temp. (Gauge ) Cooling Capacity   Input
Gauge Pressure lb/in2 kg/cm2 Kcal/Hr RT KW
  -25 14.5 1.02         354,720   117.3 198.6
  -20 21.0 1.48         419,730   138.8 204.6
  -15 28.4 2.00         524,660   173.5 209.4
30 -10 37.0 2.60         633,230   209.4 213.6
11.2kg/cm2 -5 46.6 3.28         763,560   252.5 224.3
(160 PSI) 0 57.9 4.07         946,210   312.9 224.9
  5 70.7 4.97      1,130,670   373.9 232.1
  -20 21.0 1.48         378,000   125.0 228.5
  -15 28.4 2.00         481,120   159.1 233.3
35 -10 37.0 2.60         593,310   196.2 240.5
12.9kg/cm2 -5 46.6 3.28         716,390   236.9 242.3
(184 PSI) 0 57.9 4.07         884,520   292.5 256.1
  5 70.7 4.97      1,065,660   352.4 264.4
  -20 21.0 1.48         360,160   119.1 255.5
  -15 28.4 2.00         454,200   150.2 261.4
40 -10 37.0 2.60         562,770   186.1 265.0
14.7kg/cm2 -5 46.6 3.28         687,360   227.3 270.4
(210 PSI) 0 57.9 4.07         844,910   279.4 278.2
  5 70.7 4.97      1,013,040   335.0 284.2
  -15 28.4 2.00         419,730   138.8 287.8
45 -10 37.0 2.60         515,590   170.5 291.3
16.7kg/cm2 -5 46.6 3.28         629,600   208.2 297.3
(239 PSI) 0 57.9 4.07         777,770   257.2 307.5
  5 70.7 4.97         940,770   311.1 315.9
註:1.冷凍特性試驗係依據吸入冷媒蒸氣過熱10℃,冷媒液體超冷5℃.
             ※正常運轉時請調整冷媒蒸氣過熱溫度約5℃比較適合.
     2.使用於蒸發溫度-15℃以下時,高壓部將產生超高溫會影響冷凍油使之稀薄,需要增加裝置油冷卻器.
             (Economizer Cooler)
     .可容許檢驗值±5%.
NOTE:1.The Refrigerating Performance Based on 10 Suction Superheat , 5 Liquid Subcooling. 
           2.The Suction Temp. below - 15 is in need of oil cooler (Economizer cooler).
           3.Permissible Inspection Value±5%.